Naming Lights and Setting Rated Power¶
Overview¶
After adding lights to your network, you should give them meaningful names and set their rated power for accurate energy monitoring. Descriptive names make it easy to identify specific fixtures when creating groups, scenes, or troubleshooting issues.
Why Naming Matters¶
Clear, descriptive names help you:
- Quickly identify specific fixtures in the app
- Create logical groups and scenes
- Troubleshoot issues efficiently
- Document your installation for future maintenance
- Hand off projects to facility managers
Example: Instead of "Light 001," use names like "Conference Room A - North" or "Hallway Light 3."
Renaming a Light¶
Step-by-Step Instructions¶
- Navigate to the Lights page.
- Tap a light's icon to turn it on or off—this helps you identify the physical fixture.
- Long press (press and hold) on the light's icon to open the Light Dimming settings page.
- Tap the light's name in the upper left corner of the screen.
- Enter the new name in the dialog box that appears.
- Tap OK to save.
The light now displays with its updated name on the Lights page.
Using Suggested Names¶
When entering names, the app may suggest names based on your previous entries. Tap a suggestion to use it quickly—this speeds up naming when you have many similar lights.
Naming Best Practices¶
| Approach | Example Names |
|---|---|
| Location-based | "Conf Room A - North", "Hallway 3 - East" |
| Numbered sequence | "Open Office 01", "Open Office 02" |
| Function-based | "Reception Desk", "Server Room Main" |
| Grid reference | "Bay A-3", "Row 2 Column 5" |
Tips for Effective Naming¶
- Use a consistent naming convention across your installation
- Include location identifiers (building, floor, room)
- Keep names concise but descriptive
- Consider how names will appear in groups and scenes
- Document your naming scheme for future reference
Setting Rated Power¶
Rated power (wattage) enables accurate energy monitoring across your installation. The system uses this value to calculate and report actual energy consumption.
Step-by-Step Instructions¶
- Long press on a light's icon to open the Light Dimming settings page.
- Locate the wattage field on this page.
- Enter the fixture's full rated wattage: its power at 100% output, with no trim applied.
- The setting saves automatically.
Important: Enter the Full Wattage, Even With a High-End Trim¶
Always enter the fixture's full rated wattage, measured at 100% output with no trim. Do not reduce it for a high-end trim. The app already applies the trim when it calculates energy:
Power = Rated Power × High-end Trim × Light Level
| Scenario | What to Enter | What the App Calculates at Full Brightness |
|---|---|---|
| No trim applied | 30W | 30W |
| 80% high-end trim on 30W fixture | 30W | 24W (30 × 0.80) |
| 90% high-end trim on 40W fixture | 40W | 36W (40 × 0.90) |
| 70% high-end trim on 50W fixture | 50W | 35W (50 × 0.70) |
Earlier versions of this guide said the opposite
This page previously said to enter the wattage after trim. That counts the trim twice: a 30W fixture at 80% trim entered as 24W is reported at 19.2W instead of 24W. If you followed the earlier instruction, re-enter the full fixture wattage.
Where to Find Fixture Wattage¶
- Check the fixture label
- Refer to the product specification sheet
- Consult installation documentation
Quick Reference¶
| Task | Steps |
|---|---|
| Rename a light | Long press → Tap name → Enter new name → OK |
| Set rated power | Long press → Enter wattage value |
| Identify light first | Tap icon to flash fixture |
Common Mistakes to Avoid¶
| Mistake | Correct Approach |
|---|---|
| Using generic names | Use descriptive, location-based names |
| Entering the trimmed wattage (e.g. 24W for a 30W fixture at 80% trim) | Enter the full wattage at 100% output; the app applies the trim |
| Inconsistent naming | Follow a consistent naming convention |
| Not documenting names | Keep a record of your naming scheme |