Recommended Settings by Space Type

Use these as starting points when configuring sensors, dimming, and controls for common commercial spaces, then fine-tune to the project's requirements.

Starting points, not a substitute for design

These values are typical recommendations. Always follow the project's Control Intent Narrative and Sequence of Operations and the applicable local energy code (e.g., ASHRAE 90.1, Title 24).

Settings by space type

Space 1st Time Delay (T1) 2nd Time Delay (T2) Dim Level Linkage Light Level Scenes Wall Switches
Open office 20 min 1 min 50% 50% None A button programmed to ALL OFF for quickly turning off lights when leaving
Meeting room 20 min 1 min 80% 80% Configure Presentation / Lecture scenes Associate the scenes to a SCENE button
Classroom 30–40 min 5 min 80% 80% Configure Presentation / Lecture scenes Associate the scenes to a SCENE button
Storage room 10 min 1 min 30% 80% None None
Corridor 10 min 1 min – Infinity 30% 50% None None